1Instruction ManualPRINTED 0114 326464-000KEEP THIS MANUAL IN THE POCKET ON HEATER FOR FUTURE REFERENCE WHENEVER MAINTENANCE ADJUSTMENT OR SERVICE IS
10 * CAUTION HARNESS HAS 120 VAC. IN OPERATION. ** See Planning the Vent System, Installation of Vent System and Condensate Piping for more informat
21CHAUFFAGE DES LOCAUX ET SYSTÈME D’EAU POTABLEVotre chauffe-eau est muni de connexions d’entrée/de sortie pour être utilisé dans des applications de
20SYSTÈMES D’ALIMENTATION AU GAZLes systèmes d’alimentation en gaz à basse pression sont définis comme des systèmes qui ne peuvent en aucune circonsta
19MÉLANGEURSBRÛLURECHAUDDes températures d’eau supérieures à 52 °C (125 °F) peuvent provoquer de graves brûlures, résultant instantanément en blessure
18EXIGENCES D’INSTALLATIONCORROSION DES VAPEURS CHIMIQUESLa corrosion des conduits de cheminée et du système de ventilation peut se produire si l’air
17Subsidiairement, une ouverture unique permanente, commençant à 300 mm (12 po) du haut de l’enceinte, sera fournie. Voir Figure 6. Le chauffe-eau doi
16ESPACE NON CONFINÉUn espace non confiné est un espace dont le volume N’EST PAS INFÉRIEUR À 4,8 m3/kW (50 pi3/1 000 Btu/h) du débit calorifique total
15AVERTISSEMENTRisque d’incendie ou d’explosionLire le manuel d’utilisation avant d’installer, d’utiliser ou d’entretenir le chauffe-eau.• Une mauvais
14EMPLACEMENT DU CHAUFFE-EAUChoisir soigneusement un emplacement pour le nouveau chauffe-eau. L’emplacement est une considération extrêmement importan
13COMMANDES ET INTERRUPTEURSCe modèle est équipé de trois manostats. Ces interrupteurs sont essentiels pour l’opération sécuritaire et adéquate de l’a
12CARACTÉRISTIQUES ET COMPOSANTS (SUITE) 1: Ensemble des circuits de commande 2: Manostat de l’entrée d’air 3: Manostat de l’évacuation d’
11 * CAUTION HARNESS HAS 120 VAC. IN OPERATION. ** See Planning the Vent System, Installation of Vent System and Condensate Piping for more informat
11RENIFLARD*INSTALLER CONFORMÉMENT AUX CODES LOCAUXUNITÉ 75 GALLONCARACTÉRISTIQUES ET COMPOSANTS (SUITE)24183531942319222321112172511**2951821201626,
10 Figure 1B : UNITÉ 50 GALLONRENIFLARD*INSTALLER CONFORMÉMENT AUX CODES LOCAUXUNITÉ 50 GALLONCARACTÉRISTIQUES ET COMPOSANTS24183531942319**2920222321
9DONNÉES SUR LES DIMENSIONS ET LA CAPACITÉ TABLE 2 – CAPACITÉ ET CARACTÉRISTIQUES ÉLECTRIQUES ET DE GAZCapacité approximative Pression du collecteur C
8DONNÉES SUR LES DIMENSIONS ET LA CAPACITÉDIMENSIONS DE MISE EN PLACE : UNITÉ 50 GALLON Figure 1A : DIMENSIONS POUR UNITÉ 75 GALLONDIMENSIONS DE MISE
7Merci d’avoir fait l’achat de ce chauffe-eau. Correctement installé et maintenu, il fonctionnera sans ennui pendant des années.ABRÉVIATIONS UTILISÉES
6INFORMATIONS DE SÉCURITÉ GÉNÉRALESDanger d’incendieAVERTISSEMENTPour assurer une protection continuelle contre les risques d’incendie :Ne pas install
5INFORMATION DE SÉCURITÉ GÉNÉRALE• Avant d’effectuer un entretien sur le chauffe-eau, s’assurer que l’ensemble de la soufflante est débranché ou que l
4PRÉCAUTIONSNE PAS UTILISER CE CHAUFFE-EAU SI L’UN QUELCONQUE DE CES COMPOSANTS A ÉTÉ SOUS L’EAU. Appeler immédiatement un organisme de service qualif
3L’installation, l’utilisation et l’entretien appropriés de ce chauffe-eau sont extrêmement importants pour la sécurité du propriétaire et celle d’aut
2TABLE DES MATIÈRESINSTALLATION, UTILISATION ET SERVICE EN TOUTE SÉCURITÉ ...
12FEATURES AND COMPONENTS (CONT.) 1: Control Assembly 2: Blocked Intake Switch 3: Blocked Outlet Switch 4: Blower Prover Switch 5: B
1Manuel d’utilisationIMPRIMÉ 0114 326464-000MODÈLES AU GAZ À VENTILATION FORCÉE/VENTILATION DIRECTE FORCÉE AVEC ALLUMAGE À ÉTINCELLE DIRECTEMODÈLES 6
13CONTROLS AND SWITCHESThis model is provided with three pressure switches. These switches are essential to the safe and proper operation of the unit.
14LOCATING THE WATER HEATERCarefully choose a location for the new water heater. The placement is a very important consideration for the safe
15Minimum clearances between the water heater and combustible construction are 0 inch at the sides and rear, 5.5” (14.0 cm) from the fr
16UNCONFINED SPACEAn Unconned Space is one whose volume IS NOT LESS THAN 50 cubic feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the
17Alternatively a single permanent opening, commencing within 12 inches (300 mm) of the top of the enclosure, shall be provided. See Figure
18INSTALLATION REQUIREMENTSCHEMICAL VAPOR CORROSIONCorrosion of the ueways and vent system may occur if air for combustion contains certai
19MIXING VALVESWater temperature over 125°F (52°C)can cause severe burns instantlyresulting in severe injury or death.Children, the elderly and thephy
2TABLE OF CONTENTSSAFE INSTALLATION, USE AND SERVICE...3APPROVALS ...
20GAS SUPPLY SYSTEMSLow pressure building gas supply systems are dened as those systems that cannot under any circumstances exceed 14” W.C.
21SPACE HEATING AND POTABLE WATER SYSTEMYour water heater is equipped with inlet/outlet connections for use in space heating applications (see Figure
22Water Damage HazardTemperature-Pressure Relief Valve dischargepipe must terminate at adequate drain.•CAUTIONT&P VALVE DISCHARGE PIPE REQUIREMENT
23CONDENSATE PIPINGThis water heater is a condensing unit and requires a drain to be located in close proximity to allow the condensate to drain safel
24VENT INSTALLATION CONSIDERATIONSThis water heater can be vented using room air for intake combustion air, or direct vented so that all int
25POLYPROPYLENE INSTALLATIONSThe water heater has been approved to be installed with Polypropylene vent material as shown in Table 5 and Tabl
26INSTALLATION OF HORIZONTAL THROUGH THE WALL VENT SYSTEMIf you are installing your system so that it vents through roof, please refer to section titl
27DIRECT VENT TERMINAL INSTALLATIONThe air intake provided on the unit contains an air intake screen to prevent large particles from entering the unit
28TERMINATION CLEARANCES SIDEWALL POWER VENTV XVENT TERMINAL AIR SUPPLY INLETAREA WHERE TERMINAL IS NOT PERMITTEDvvAGVFIXEDCLOSEDFIXEDCLOSEDOPERABLEOP
29TERMINATION CLEARANCES SIDEWALL DIRECT VENTV XVENT TERMINAL AIR SUPPLY INLETAREA WHERE TERMINAL IS NOT PERMITTEDvvAGVFIXEDCLOSEDFIXEDCLOSEDOPERABLEO
3The proper installation, use and servicing of this water heater is extremely important to your safety and the safety of others.Many safety-related me
30VERTICAL VENT TERMINAL INSTALLATIONWHEN TERMINATING THROUGH A ROOF, THE FOLLOWING SPECIFICATIONS PERTAINING TO TERMINAL LOCATION MUST BE FOLLOWED.1.
3112” MINIMUM CLEARANCE ABOVE HIGHESTANTICIPATED SNOW LEVEL12” MINIMUM CLEARANCEABOVE HIGHEST ANTICIPATEDSNOW LEVEL24” MINIMUM SEPARATION. EXHAUSTMUST
32CONCENTRIC VENT INSTALLATIONThis water heater is certied for concentric venting with concentric vent kit #9006328005. Follow instructions belo
33NOTE: Do not allow insulation or other materials to accumulate inside pipe assembly when installing through hole.5. Secure assembly to roo
345. Install rain cap and small diameter pipe assembly in Y concentric tting and large pipe assembly. Ensure small diameter pipe is bottomed and c
35LOW PROFILE TERMINATION INSTALLATIONThis water heater is certied for sidewall direct venting with IPEX System 636 Low Prole Vent Kit. Fo
36LIGHTING AND OPERATION LABELS
37Valves for reducing the point-of-use temperature by mixing cold and hot water are available. Also available are inexpensive devices that attach to f
38THE DESKTOP SCREENDuring normal operation the control system will display the Desktop screen on the LCD which is the default screen. The control sys
39STATUS ICONSThe Status Icons are displayed on the Desktop screen and convey operational and diagnostic information. The icons are described in the t
4PRECAUTIONSDO NOT USE THIS WATER HEATER IF ANY PART HAS BEEN UNDER WATER. Immediately call a qualied service agency to inspect the water hea
40OPERATING STATESThe current operational state of the water heater is displayed on the Desktop screen as the Status. The common operational states ar
41USER SETTINGS & CONTROL SYSTEM MENUSTEMPERATURESOPERATING SET POINT AND DIFFERENTIAL ADJUSTMENTThe Operating Set Point is adjustable from 90°F (
42TEMPERATURES (CONT)DESCRIPTION/ACTION DISPLAY• Tank Probe Offset - adjustable user setting, range -5° to +5°F (factory setting 0°F). The Tank Pro
43DISPLAY SETTINGSDESCRIPTION/ACTION DISPLAYSelect Display Settings from the Main Menu and press the Operational Button under "SELECT&qu
44CURRENT FAULTDESCRIPTION/ACTION DISPLAYSelect Current Fault from the Main Menu and press the Operational Button under "SELECT" to enter th
45SERVICE CONTACT INFORMATIONThe control system has a discrete menu that Installing contractors and/or qualied service technician can access to enter
46START UP CONDITIONSSMOKE/ODORIt is not uncommon to experience a small amount of smoke and odor during the initial start-up. This is due to burning o
47VENTING SYSTEM INSPECTIONAt least once a year a visual inspection should be made of the venting system. You should look for:1. Obstructions which
48POWERED ANODE ROD (OPTIONAL MODELS)To insure a long, trouble-free operating life, certain models of water heaters covered in this manual are factory
49TO DRAIN THE WATER HEATER STORAGE TANK:1. Turn off the electrical supply to the water heater.2. Turn off the gas supply at the Main Gas Shutof
5GENERAL SAFETY INFORMATION
50Never use this water heater unless it is completely lled with water. To prevent damage to the tank, the tank must be lled with water. Water must
51TROUBLESHOOTINGSEQUENCE OF OPERATIONRead the Sequence of Operation below before attempting to correct any operational problems. See the Sequ
52SEQUENCE OF OPERATION FLOW CHARTYES NOWater is heated to set point24 V Gas Valvede-energized60 secondInter-Purge cycle24 V Gas Valvede-energizedRetr
53If the Main Burner ignites momentarily but does not sustain ignition allow the water heater to try to ignite up to two more times until con
54Only qualied service technician, as dened in Qualications using appropriate test equipment, should perform any service procedures on the water he
55FAULT AND ALERT MESSAGESCall the technical support phone number listed on the back cover for further technical assistance or to locate a qualied se
56FAULT AND ALERT MESSAGES (CONT)Call the technical support phone number listed on the back cover for further technical assistance or to locate a qual
57 CAUTIONLABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. VERIFY PROPER OPE
58NOTES
59THIS WARRANTY IS APPLICABLE TO THE ORIGINAL OWNER ONLY. If the glass lined tank in this water heater shall prove upon examination by (the warrantor
6Fire HazardDo not install water heater oncarpeted floor.Do not operate water heater ifflood damaged.For continued protection againstrisk of fire:Fire
60GSW Water Heating599 Hill Street WestFergus, ON Canada N1M 2X1Should you have any questions pleaseEmail us at [email protected] orVisit our web
60GSW Water Heating599 Hill Street WestFergus, ON Canada N1M 2X1Si vous avez des questions, veuillezEnvoyez un courriel à [email protected] ouVis
59a. Les frais de main d’œuvre pour la réparation, la dépose ou la réinstallation du chauffe-eau ou de tout composant;b. Les frais d’expédition et de
58REMARQUES
57 ATTENTIONLORSQU’ UN ENTRETIEN EST EFFECTUÉ SUR LES COMMANDES, ÉTIQUETER TOUS LES FILS AVANT DE FAIRE LES DÉBRANCHEMENTS. DES ERREURS DE FILAGE PEUV
56MESSAGES DE DÉFAILLANCE ET D’ALERTE (SUITE)Composer le numéro de téléphone du soutien technique indiqué sur la couverture arrière pour une assistanc
55MESSAGES DE DÉFAILLANCE ET D’ALERTEComposer le numéro de téléphone du soutien technique indiqué sur la couverture arrière pour une assistance techni
54Seulement un technicien de service qualifié, tel que défini dans la section Qualifications, utilisant un équipement de tests approprié, devrait effe
53Si le brûleur principal s’allume pendant une courte durée mais ne soutient pas l’allumage, laisser le chauffe-eau essayer de s’allumer jusqu’à deux
52ORGANIGRAMME DE SÉQUENCE DE FONCTIONNEMENTOUI NONL’eau est chauffée au point de consigneLe régulateur de gaz 24 V est mis hors tensionCycle inter-vi
7Thank You for purchasing this water heater. Properly installed and maintained, it should give you years of trouble free service.ABBREVIATIONS USEDAbb
51DÉPANNAGESÉQUENCE DE FONCTIONNEMENTLire la section Séquence de fonctionnement avant de tenter de rectifier tout problème opérationnel. Voir l’Organi
50Ne jamais faire fonctionner ce chauffe-eau s’il n’est pas complètement rempli d’eau. Pour prévenir des dommages au réservoir, ce dernier doit être r
49POUR VIDANGER LE RÉSERVOIR DE STOCKAGE DU CHAUFFE-EAU :1. Couper l’alimentation électrique au chauffe-eau.2. Fermer l’alimentation en gaz au robine
48TIGE D’ANODE ALIMENTÉE (CERTAINS MODÈLES)Pour assurer une durée de vie utile longue et sans problème, certains modèles de chauffe-eau traités dans c
47INSPECTION DU RÉSEAU DE VENTILATION• Du gaz de carneau pourrait s’échapper si le tuyau de l’évent n’est pas connecté.• Soyez à l’affût de tout systè
46CONDITIONS DE DÉMARRAGEFUMÉE/ODEURIl n’est pas inhabituel de voir une petite quantité de fumée et une odeur se dégager durant le démarrage initial.
45INFORMATION DE CONTACT DE SERVICELe système de commande a un menu discret auquel les entrepreneurs d’installation et/ou les techniciens de service q
44DÉFAILLANCE DE COURANTDESCRIPTION/ACTION AFFICHAGESélectionner Défaillance de courant à partir du Menu principal et appuyer sur le bouton Opérationn
43RÉGLAGES D’AFFICHAGEDESCRIPTION/ACTION AFFICHAGESélectionner Paramètres d’affichage à partir du Menu principal et appuyer sur le bouton Opérationnel
42TEMPÉRATURES (SUITE)DESCRIPTION/ACTION AFFICHAGE• « Tank Probe Offset » (Décalage Sonde du réservoir) - paramètre réglable par l’utilisateur, fourc
8DIMENSIONS AND CAPACITY DATAROUGH IN DIMENSIONS: 50 GALLON UNITFigure 1A: DIMENSIONS FOR 75 GALLON UNITROUGH IN DIMENSIONS: 75 GALLON UNITFigure 1: D
41PARAMÈTRES D’UTILISATEUR ET MENUS DU SYSTÈME DE COMMANDETEMPÉRATURESPOINT DE CONSIGNE DE FONCTIONNEMENT ET RÉGLAGE DIFFÉRENTIELLe point de consigne
40ÉTATS DE FONCTIONNEMENTL’état de fonctionnement courant du chauffe-eau s’affiche sur l’écran Bureau comme État. Les états de fonctionnement communs
39ICÔNES ÉTATLes icônes État s’affichent sur l’écran Bureau et transmettent une information opérationnelle et de diagnostic. Les icônes sont décrites
38L’ÉCRAN DE BUREAUPendant le fonctionnement normal, le système de commande affichera l’écran Bureau sur le LCD qui est l’écran par défaut. Le système
37La Table ci-dessous indique la relation temps-brûlure approximative pour la peau normale adulte. Des cycles de chauffage répétés courts causés par d
36ÉTIQUETTES POUR L’ALLUMAGE ET LE FONCTIONNEMENT321128-000CHAUDBRûLUREcommande en position ARRÊT.6. Cet appareil est muni d'un dispositif d&apo
35INSTALLATION DE TERMINAISON PROFIL BASCe chauffe-eau est certifié pour une ventilation directe à paroi latérale avec la trousse de ventilation profi
345. Installer le capuchon de pluie et l’ensemble tuyau de petit diamètre dans l’ensemble raccord concentrique en Y et tuyau le plus gros. S’assurer
33REMARQUE : Ne pas laisser l’isolation ou autres matériaux s’accumuler à l’intérieur de l’ensemble tuyau lors de l’installation à travers le trou.5.
32INSTALLATION DE VENTILATION CONCENTRIQUECe chauffe-eau est certifié pour une ventilation concentrique avec la trousse de ventilation concentrique #9
9DIMENSIONS AND CAPACITY DATATable 2 – CAPACITY, GAS AND ELECTRICAL CHARACTERISTICSApproximate Capacity Manifold Pressure Electrical CharacteristicsU.
3112” MINIMUM CLEARANCE ABOVE HIGHESTANTICIPATED SNOW LEVEL12” MINIMUM CLEARANCEABOVE HIGHEST ANTICIPATEDSNOW LEVEL24” MINIMUM SEPARATION. EXHAUSTMUST
30INSTALLATION D’UNE BOUCHE DE VENTILATION VERTICALEAVEC UNE TERMINAISON À TRAVERS UN TOIT, LES SPÉCIFICATIONS SUIVANTES AU SUJET DE L’EMPLACEMENT DU
29RÈGLES D’IMPLANTATION D’UN TERMINAL MURAL À VENTILATION DIRECTV XTERMINAISON DE VENTILATION BOUCHE D’ADMISSION D’AIR ZONE DANS LAQUELLE BORNE N’EST
28TERMINAISON DÉGAGEMENTS PAROI LATÉRALE VENTILATION À AIR PULSÉV XTERMINAISON DE VENTILATION BOUCHE D’ADMISSION D’AIR ZONE DANS LAQUELLE BORNE N’EST
27INSTALLATION D’UNE BOUCHE DE VENTILATION DIRECTEL’entrée d’air fournie sur l’appareil contient une grille d’entrée d’air afin d’empêcher les grosses
26INSTALLATION D’UN SYSTÈME DE VENTILATION HORIZONTAL À TRAVERS LE MURSi vous installez votre système de sorte qu’il ventile à travers le toit, consul
25INSTALLATIONS AVEC POLYPROPYLÈNELe chauffe-eau a été approuvé pour être installé avec du matériau de ventilation en polypropylène tel qu’illustré da
24• Installer le système de ventilation conformément à ces instructions et aux codes locaux.• Ne pas utiliser le chauffe-eau s’il a été endommagé par
23TUYAUTERIE DE CONDENSATCe chauffe-eau est un appareil à condensation et nécessite une vidange installée à proximité immédiate et ce, pour permettre
22d’évacuation n’est pas connectée à un drain ou autres moyens adéquats, le débit d’eau peut provoquer des dommages matériels.Risque de dommages par l