SÉQUENCE DE FONCTIONNEMENT DU LOGICIEL
SÉQUENCE DE FONCTIONNEMENT DU LOGICIEL DU MODULE DE LA COMMANDE
D’ALLUMAGE
OUI
OUI
OUI
OUI
OUI
OUI
OUI
OUI
OUI
NON
NON
OUI
NON
NON
NON
OUI
NON
NON
NON
NON
NON
NON
OUI
DÉMARRER
RÉGLER LE THERMOSTAT
(EN ATTENTE)
LE
THERMOSTAT EST-IL
SATISFAIT?
CONTRÔLER LA MISE
EN FONCTION
LE MANOSTAT
EST-IL OUVERT?
(TEST DU MANOSTAT)
METTRE LE VENTILATEUR
EN MARCHE.
LE MANOSTAT
EST-IL FERMÉ? (TIRAGE INITIAL
DE VÉRIFICATION)
PRÉ-PURGE DE 6 SECONDES
APRÈS QUE LE MANOSTAT
SE FERME
PURGE DE
60 SECONDES.
INTER-PURGE DE
45 SECONDES
ARRÊTER LE VENTILATEUR ET METTRE
EN MARCHE L’ALLUMEUR POUR UN
RÉCHAUFFEMENT DE 35 SECONDES
(SA MISE EN TRAIN)
LE MANOSTAT
EST-IL OUVERT?
METTRE LE VENTILATEUR ET LE
RÉGULATEUR DE GAZ EN MARCHE
PENDANT 3 SECONDES (TIRAGE FINAL DE
VÉRIFICATION/ÉTABLISSEMENT DE LA FLAMME)
ÉTEINDRE L’ALLUMEUR POUR UNE PÉRIODE
DE VÉRIFICATION DE LA FLAMME D’1
SECONDE. LE VENTILATEUR ET LE RÉGULATEUR
DE GAZ DEMEURENT EN MARCHE.
Y A-T-IL UNE FLAMME?
ARRÊTER LE RÉGULATEUR DE GAZ.
ÉTAIT-CE LA
3
ÈME
TENTATIVE?
ÉTAIT-CE LA 4
ÈME
SÉQUENCE? (À SAVOIR
12 ESSAIS AU TOTAL
POUR L’ALLUMAGE)
VERROUILLAGE
TEMPORAIRE –
RÉINITIALISATION APRÈS
60 MINUTES
VERROUILLAGE PERMANENT.
ARRÊTER LE VENTILATEUR PENDANT 60 SECONDES.
LE MANOSTAT EST-IL
FERMÉ AU BOUT
DE 60 SECONDES?
AUCUNE FLAMME.
EST-CE QUE LE
RÉGULATEUR DE GAZ
EST HORS FONCTION EN
RAISON DU MANOSTAT
QUI EST OUVERT?
ARRÊTER LE RÉGULATEUR DE GAZ.
LA FLAMME EST-ELLE
PRÉSENTE ET LE MANOSTAT
EST-IL FERMÉ?
ÉTAT DE CHAUFFAGE STABLE
JUSQU’À CE QUE LE THERMOSTAT
SOIT SATISFAIT.
LE MANOSTAT EST-IL FERMÉ?
IGNORER LE MANOSTAT
PENDANT 5 SECONDES.
LE THERMOSTAT
EST-IL SATISFAIT?
ARRÊTER LE RÉGULATEUR DE GAZ.