-For sidewall terminaons-
-For rooop terminaons-
Formultiplesidewallexhaustterminations(e.g.multi-unit
systems),anexhaustterminationmustbeatleast305mm
(1ft.)awayfromanotherexhausttermination.Anexhaust
termination must also be at least 610 mm (2 ft.) away
fromaninsidecorner.(iftheadjacentwallislessthan610
mm(2ft.)oflength,theminimumrequireddistanceaway
fromtheinsidecornerwillbeequaltothelengthofthat
adjacentwall.)
For multiple-unit, direct-vent sidewall terminations that
combine the intake and exhaust into a single penetration,
spaceeachdirect-ventterminationatleast305mm(1ft.)
awayfromeachother,nomattertheorientation.Adirect-
ventterminationmustalsobeatleast610mm(2ft.)away
fromaninsidecorner.(iftheadjacentwallislessthan610
mm(2ft.)oflength,theminimumrequireddistanceaway
fromtheinsidecornerwillbeequaltothelengthofthat
adjacentwall.)
For multiple-unit rooftop terminations (whether for standard or direct-vent installations) space all
exhaustandintaketerminationsinaccordancewithlocalcodes.Anexhaustterminationmustbespaced
fromawallorsurfaceinaccordancewithlocalcodesaswell.Intheabsenceofsuchacode,anexhaust
terminationmustbeahorizontaldistanceofatleast610mm(2ft.)awayfromawallorsurface.
Exhaust and/or
direct-vent sidewall
terminations should
be at least 610 mm
(2 ft.) away from an
opposite surface/
wall.Donotplacethe
termination directly
in front of an opening
into a building
.
610 mm
(2ft.)
Exhaust
termination
Please follow all local and national codes in regards to proper termination
clearances. In the absence of such codes, the above clearances can be used as
guidelines. Local codes supersede these guidelines.
CAUTION
Installaon
Exhaust
termination
Inside
corner
305 mm
(1ft.)
610 mm
(2ft.)
305 mm
(1ft.)
Installaon Manual
A:Inaccordancewithlocalcodes
Air intake
A
Exhaustterminaon
A
A
A
A
Air intake
610 mm
(2)
Exhaust
terminaon
For direct-vent sidewall
terminationsthatusetwo
separate penetrations for
the intake and exhaust,
distance the intake and
exhaust terminations at
least915mm(3ft.)away
from each other, no
matter the orientation.
915
mm
(3ft.)
Air supply inlet
915 mm
(3ft.)
915 mm
(3ft.)
Exhaust
termination
Combined
intake and
exhaust
termination
Inside
corner
305 mm
(1ft.)
610 mm
(2ft.)
305 mm
(1ft.)